🇵🇱 SIEĆ BADAWCZA ŁUKASIEWICZ - INSTYTUT ELEKTROTECHNIKI PL
ConstructionMaterials & polymersElectronics & EMCEnvironment
SIEĆ BADAWCZA ŁUKASIEWICZ - INSTYTUT ELEKTROTECHNIKI is a laboratory accredited by PCA under number AB 074 (Warszawa, Poland). Its accreditation scope covers 96 test methods in the following areas: Construction, Materials & polymers, Electronics & EMC, Environment. Test objects include: Enclosures for electrical equipment, Electrical and electronic equi…, AC metal-enclosed switchgear for rated voltages above 1 kV and up t…, Low-voltage switchgear and control gear assemblies, Alternating-current high-voltage circuit-breakers.
At a glance
- Accreditation number: PCA AB 074
- Methods in scope: 96
- Types of test objects: 27
- City: Warszawa, Poland
- Accreditation number
- AB 074
- Accreditation body
- PCA
- Address
- LABORATORIUM BADAWCZE APARATURY ELEKTROENERGETYCZNEJ (LAE), ul. Pożaryskiego 28, 04-703 Warszawa
- City
- Warszawa, Poland
What this laboratory tests (27)
- Enclosures for electrical equipment, Electrical and electronic equipment — 8 methods
- AC metal-enclosed switchgear for rated voltages above 1 kV and up to and including 52 kV, AC insulation-enclosed switchgear for rated voltages above 1 kV and up to and including 38 kV, Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV — 7 methods
- Low-voltage switchgear and control gear assemblies — 7 methods
- Alternating-current high-voltage circuit-breakers — 6 methods
- Automatic circuit reclosers and fault interrupters for alternating current systems up to and including 38 kV, High-voltage alternating current disconnectors and earthing switches — 6 methods
- High-voltage alternating current switch-fuse combinations — 6 methods
- High-voltage alternating current switches for rated voltages up to and including 52 kV — 6 methods
- Contactors and motor-starters — 5 methods
- Current transformers, Voltage transformers, Combined transformers — 5 methods
- Low-voltage switches, disconnectors, switch-disconnectors and fuse-combination units, Low-voltage control circuit devices and switching elements - electromechanical control circuit devices, Low-voltage multiple function equipment - transfer switching equipment — 5 methods
- Alternating current high-voltage contactors — 4 methods
- High-voltage/low-voltage prefabricated substations — 4 methods
- HV metal-enclosed busbars — 4 methods
- Reactors and transformers — 4 methods
- Alternating-current low-voltage circuit-breakers — 3 methods
- and 12 more
Laboratory locations
- SIEĆ BADAWCZA ŁUKASIEWICZ - INSTYTUT ELEKTROTECHNIKI (main site) — ul. Pożaryskiego 28, 04-703 Warszawa
- HIGH POWER EQUIPMENT TESTING LABORATORY (LAE)
Certificate information
- Issue date
- 07.01.2026
- Issue no.
- 26
Accreditation scope — test methods (96)
| No. | Test object | Methodology / Parameters | Technique | Reference document | |
|---|---|---|---|---|---|
| High Power Equipment Testing Laboratory (LAE) | |||||
| 1 | Alternating-current high-voltage circuit-breakers | Impulse voltage withstand test: lightning impulse up to Up = 1200 kV power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-100:2022-04 | IEC 62271-100:2021 | PN-EN IEC 62271-101:2022-04 | IEC 62271-101:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 2 | Alternating-current high-voltage circuit-breakers | Temperature rise tests Range up to 12 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-100:2022-04 | IEC 62271-100:2021 | PN-EN IEC 62271-101:2022-04 | IEC 62271-101:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 3 | Alternating-current high-voltage circuit-breakers | Main circuit resistance Range from 10-5 Ω Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-100:2022-04 | IEC 62271-100:2021 | PN-EN IEC 62271-101:2022-04 | IEC 62271-101:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 4 | Alternating-current high-voltage circuit-breakers | Short-circuit tests Range up to 120 kA rms / 300 kA peak Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-100:2022-04 | IEC 62271-100:2021 | PN-EN IEC 62271-101:2022-04 | IEC 62271-101:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 5 | Alternating-current high-voltage circuit-breakers | Mechanical operation and mechanical endurance Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-100:2022-04 | IEC 62271-100:2021 | PN-EN IEC 62271-101:2022-04 | IEC 62271-101:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 6 | Alternating-current high-voltage circuit-breakers | Making and breaking capacity Range up to 50 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-100:2022-04 | IEC 62271-100:2021 | PN-EN IEC 62271-101:2022-04 | IEC 62271-101:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 7 | Automatic circuit reclosers and fault interrupters for alternating current systems up to and including 38 kV, High-voltage alternating current disconnectors and earthing switches | Impulse voltage withstand test: lightning impulse up to Up = 1200 kV power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
IEC 62271-111:2019 | PN-EN IEC 62271-102:2018-10 | PN-EN IEC 62271-102:2018-10/A1:2023-01 | IEC 62271-102:2018+AMD1:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 8 | Automatic circuit reclosers and fault interrupters for alternating current systems up to and including 38 kV, High-voltage alternating current disconnectors and earthing switches | Temperature rise tests Range up to 12 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
IEC 62271-111:2019 | PN-EN IEC 62271-102:2018-10 | PN-EN IEC 62271-102:2018-10/A1:2023-01 | IEC 62271-102:2018+AMD1:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 9 | Automatic circuit reclosers and fault interrupters for alternating current systems up to and including 38 kV, High-voltage alternating current disconnectors and earthing switches | Main circuit resistance Range from 10-5 Ω Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
IEC 62271-111:2019 | PN-EN IEC 62271-102:2018-10 | PN-EN IEC 62271-102:2018-10/A1:2023-01 | IEC 62271-102:2018+AMD1:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 10 | Automatic circuit reclosers and fault interrupters for alternating current systems up to and including 38 kV, High-voltage alternating current disconnectors and earthing switches | Short-circuit tests Range up to 120 kA rms / 300 kA peak Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
IEC 62271-111:2019 | PN-EN IEC 62271-102:2018-10 | PN-EN IEC 62271-102:2018-10/A1:2023-01 | IEC 62271-102:2018+AMD1:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 11 | Automatic circuit reclosers and fault interrupters for alternating current systems up to and including 38 kV, High-voltage alternating current disconnectors and earthing switches | Mechanical operation and mechanical endurance Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
IEC 62271-111:2019 | PN-EN IEC 62271-102:2018-10 | PN-EN IEC 62271-102:2018-10/A1:2023-01 | IEC 62271-102:2018+AMD1:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 12 | Automatic circuit reclosers and fault interrupters for alternating current systems up to and including 38 kV, High-voltage alternating current disconnectors and earthing switches | Making and breaking capacity Range up to 50 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
IEC 62271-111:2019 | PN-EN IEC 62271-102:2018-10 | PN-EN IEC 62271-102:2018-10/A1:2023-01 | IEC 62271-102:2018+AMD1:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 13 | High-voltage alternating current switches for rated voltages up to and including 52 kV | Impulse voltage withstand test: lightning impulse up to Up = 1200 kV power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-103:2024-04 | IEC 62271-103:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1 :2022-06 | IEC 62271-1:2017+AMD1 :2021 | ||
| 14 | High-voltage alternating current switches for rated voltages up to and including 52 kV | Main circuit resistance Range from 10-5 Ω Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-103:2024-04 | IEC 62271-103:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1 :2022-06 | IEC 62271-1:2017+AMD1 :2021 | ||
| 15 | High-voltage alternating current switches for rated voltages up to and including 52 kV | Temperature rise tests Range up to 12 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-103:2024-04 | IEC 62271-103:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1 :2022-06 | IEC 62271-1:2017+AMD1 :2021 | ||
| 16 | High-voltage alternating current switches for rated voltages up to and including 52 kV | Short-circuit tests Range up to 120 kA rms / 300 kA peak Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-103:2024-04 | IEC 62271-103:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1 :2022-06 | IEC 62271-1:2017+AMD1 :2021 | ||
| 17 | High-voltage alternating current switches for rated voltages up to and including 52 kV | Making and breaking capacity Range up to 2500 A Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-103:2024-04 | IEC 62271-103:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1 :2022-06 | IEC 62271-1:2017+AMD1 :2021 | ||
| 18 | High-voltage alternating current switches for rated voltages up to and including 52 kV | Mechanical operation and mechanical endurance Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-103:2024-04 | IEC 62271-103:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1 :2022-06 | IEC 62271-1:2017+AMD1 :2021 | ||
| 19 | High-voltage alternating current switch-fuse combinations | Impulse voltage withstand test: lightning impulse up to Up = 1200 kV power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-105:2024-04 | IEC 62271-105:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1 :2022-06 | IEC 62271-1:2017+AMD1 :2021 | ||
| 20 | High-voltage alternating current switch-fuse combinations | Temperature rise tests Range up to 12 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-105:2024-04 | IEC 62271-105:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1 :2022-06 | IEC 62271-1:2017+AMD1 :2021 | ||
| 21 | High-voltage alternating current switch-fuse combinations | Main circuit resistance Range from 10-5 Ω Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-105:2024-04 | IEC 62271-105:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1 :2022-06 | IEC 62271-1:2017+AMD1 :2021 | ||
| 22 | High-voltage alternating current switch-fuse combinations | Short-circuit tests Range up to 120 kA rms / 300 kA peak Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-105:2024-04 | IEC 62271-105:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1 :2022-06 | IEC 62271-1:2017+AMD1 :2021 | ||
| 23 | High-voltage alternating current switch-fuse combinations | Making and breaking capacity Range up to 50 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-105:2024-04 | IEC 62271-105:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1 :2022-06 | IEC 62271-1:2017+AMD1 :2021 | ||
| 24 | High-voltage alternating current switch-fuse combinations | Mechanical operation Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-105:2024-04 | IEC 62271-105:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1 :2022-06 | IEC 62271-1:2017+AMD1 :2021 | ||
| 25 | Alternating current high-voltage contactors | Impulse voltage withstand test: lightning impulse up to Up = 1200 kV power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 62271-106:2021-09 | IEC 62271-106:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1 :2022-06 | IEC 62271-1:2017+AMD1 :2021 | ||
| 26 | Alternating current high-voltage contactors | Temperature rise tests Range up to 12 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 62271-106:2021-09 | IEC 62271-106:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1 :2022-06 | IEC 62271-1:2017+AMD1 :2021 | ||
| 27 | Alternating current high-voltage contactors | Main circuit resistance Range from 10-5 Ω Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 62271-106:2021-09 | IEC 62271-106:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1 :2022-06 | IEC 62271-1:2017+AMD1 :2021 | ||
| 28 | Alternating current high-voltage contactors | Short-circuit tests Range up to 120 kA rms / 300 kA peak Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 62271-106:2021-09 | IEC 62271-106:2021 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1 :2022-06 | IEC 62271-1:2017+AMD1 :2021 | ||
| 29 | AC metal-enclosed switchgear for rated voltages above 1 kV and up to and including 52 kV, AC insulation-enclosed switchgear for rated voltages above 1 kV and up to and including 38 kV, Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV | Impulse voltage withstand test: lightning impulse up to Up = 1200 kV power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 62271-200:2022-02 | PN-EN 62271-200:2022-02/A1:2025-04 | IEC 62271-200:2021 | IEC 62271-200:2021/AMD1:2024 | PN-EN 62271-201:2014-12 | IEC 62271-201:2014 | PN-EN IEC 62271-203:2023-02 | IEC 62271-203:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 30 | AC metal-enclosed switchgear for rated voltages above 1 kV and up to and including 52 kV, AC insulation-enclosed switchgear for rated voltages above 1 kV and up to and including 38 kV, Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV | Temperature rise tests Range up to 12 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 62271-200:2022-02 | PN-EN 62271-200:2022-02/A1:2025-04 | IEC 62271-200:2021 | IEC 62271-200:2021/AMD1:2024 | PN-EN 62271-201:2014-12 | IEC 62271-201:2014 | PN-EN IEC 62271-203:2023-02 | IEC 62271-203:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 31 | AC metal-enclosed switchgear for rated voltages above 1 kV and up to and including 52 kV, AC insulation-enclosed switchgear for rated voltages above 1 kV and up to and including 38 kV, Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV | Main circuit resistance Range from 10-5 Ω Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 62271-200:2022-02 | PN-EN 62271-200:2022-02/A1:2025-04 | IEC 62271-200:2021 | IEC 62271-200:2021/AMD1:2024 | PN-EN 62271-201:2014-12 | IEC 62271-201:2014 | PN-EN IEC 62271-203:2023-02 | IEC 62271-203:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 32 | AC metal-enclosed switchgear for rated voltages above 1 kV and up to and including 52 kV, AC insulation-enclosed switchgear for rated voltages above 1 kV and up to and including 38 kV, Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV | Short-circuit tests Range up to 120 kA rms / 300 kA peak Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 62271-200:2022-02 | PN-EN 62271-200:2022-02/A1:2025-04 | IEC 62271-200:2021 | IEC 62271-200:2021/AMD1:2024 | PN-EN 62271-201:2014-12 | IEC 62271-201:2014 | PN-EN IEC 62271-203:2023-02 | IEC 62271-203:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 33 | AC metal-enclosed switchgear for rated voltages above 1 kV and up to and including 52 kV, AC insulation-enclosed switchgear for rated voltages above 1 kV and up to and including 38 kV, Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV | Making and breaking capacity Range up to 2500 A Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 62271-200:2022-02 | PN-EN 62271-200:2022-02/A1:2025-04 | IEC 62271-200:2021 | IEC 62271-200:2021/AMD1:2024 | PN-EN 62271-201:2014-12 | IEC 62271-201:2014 | PN-EN IEC 62271-203:2023-02 | IEC 62271-203:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 34 | AC metal-enclosed switchgear for rated voltages above 1 kV and up to and including 52 kV, AC insulation-enclosed switchgear for rated voltages above 1 kV and up to and including 38 kV, Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV | Mechanical operation Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 62271-200:2022-02 | PN-EN 62271-200:2022-02/A1:2025-04 | IEC 62271-200:2021 | IEC 62271-200:2021/AMD1:2024 | PN-EN 62271-201:2014-12 | IEC 62271-201:2014 | PN-EN IEC 62271-203:2023-02 | IEC 62271-203:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 35 | AC metal-enclosed switchgear for rated voltages above 1 kV and up to and including 52 kV, AC insulation-enclosed switchgear for rated voltages above 1 kV and up to and including 38 kV, Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV | Internal arc fault tests Range up to 50 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 62271-200:2022-02 | PN-EN 62271-200:2022-02/A1:2025-04 | IEC 62271-200:2021 | IEC 62271-200:2021/AMD1:2024 | PN-EN 62271-201:2014-12 | IEC 62271-201:2014 | PN-EN IEC 62271-203:2023-02 | IEC 62271-203:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 36 | Low-voltage and high-voltage insulators | Impulse voltage withstand test: lightning impulse up to Up = 1200 kV power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60137:2018-02 | PN-EN 60383-1:2005 | PN-EN 60383-1:2024-04 | PN-EN 61109:2010 | PN-E-91062-1:1998 | PN-E-91062-2:1998 | ||
| 37 | Low-voltage and high-voltage insulators | Temperature rise tests Range up to 12 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60137:2018-02 | PN-EN 60383-1:2005 | PN-EN 60383-1:2024-04 | PN-EN 61109:2010 | PN-E-91062-1:1998 | PN-E-91062-2:1998 | ||
| 38 | Low-voltage and high-voltage insulators | Short-circuit tests Range up to 120 kA rms / 300 kA peak Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60137:2018-02 | PN-EN 60383-1:2005 | PN-EN 60383-1:2024-04 | PN-EN 61109:2010 | PN-E-91062-1:1998 | PN-E-91062-2:1998 | ||
| 39 | High-voltage/low-voltage prefabricated substations | Impulse voltage withstand test: lightning impulse up to Up = 1200 kV power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-202:2023-02 | IEC 62271-202:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | PN-G-42021:1997 | ||
| 40 | High-voltage/low-voltage prefabricated substations | Temperature rise tests Range up to 12 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-202:2023-02 | IEC 62271-202:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | PN-G-42021:1997 | ||
| 41 | High-voltage/low-voltage prefabricated substations | Short-circuit tests Range up to 120 kA rms / 300 kA peak Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-202:2023-02 | IEC 62271-202:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | PN-G-42021:1997 | ||
| 42 | High-voltage/low-voltage prefabricated substations | Internal arc fault tests Range up to 50 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 62271-202:2023-02 | IEC 62271-202:2022 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | PN-G-42021:1997 | ||
| 43 | Reactors and transformers | Resistance of windings Range from 10-4 Ω Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60076-1:2011 | IEC 60076-1:2011 | PN-EN 60076-2:2011 | IEC 60076-2:2011 | PN-EN 60076-3:2014-02 | PN-EN 60076-3:2014-02/A1:2018-09 | IEC 60076-3:2013+AMD1:2018 CSV | PN-EN 60076-4:2004 | IEC 60076-4:2002 | PN-EN 60076-5:2009 | IEC 60076-5:2006 | PN-EN 60076-6:2008 | IEC 60076-6:2007 | PN-EN IEC 60076-11:2019-01 | IEC 60076-11:2018 | ||
| 44 | Reactors and transformers | Temperature rise tests Range up to 4 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60076-1:2011 | IEC 60076-1:2011 | PN-EN 60076-2:2011 | IEC 60076-2:2011 | PN-EN 60076-3:2014-02 | PN-EN 60076-3:2014-02/A1:2018-09 | IEC 60076-3:2013+AMD1:2018 CSV | PN-EN 60076-4:2004 | IEC 60076-4:2002 | PN-EN 60076-5:2009 | IEC 60076-5:2006 | PN-EN 60076-6:2008 | IEC 60076-6:2007 | PN-EN IEC 60076-11:2019-01 | IEC 60076-11:2018 | ||
| 45 | Reactors and transformers | Impulse voltage withstand test: lightning impulse up to Up = 1200 kV switching impulse up to Up = 900 kV power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60076-1:2011 | IEC 60076-1:2011 | PN-EN 60076-2:2011 | IEC 60076-2:2011 | PN-EN 60076-3:2014-02 | PN-EN 60076-3:2014-02/A1:2018-09 | IEC 60076-3:2013+AMD1:2018 CSV | PN-EN 60076-4:2004 | IEC 60076-4:2002 | PN-EN 60076-5:2009 | IEC 60076-5:2006 | PN-EN 60076-6:2008 | IEC 60076-6:2007 | PN-EN IEC 60076-11:2019-01 | IEC 60076-11:2018 | ||
| 46 | Reactors and transformers | Short-circuit tests Range up to 40 kA rms / 100 kA peak Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60076-1:2011 | IEC 60076-1:2011 | PN-EN 60076-2:2011 | IEC 60076-2:2011 | PN-EN 60076-3:2014-02 | PN-EN 60076-3:2014-02/A1:2018-09 | IEC 60076-3:2013+AMD1:2018 CSV | PN-EN 60076-4:2004 | IEC 60076-4:2002 | PN-EN 60076-5:2009 | IEC 60076-5:2006 | PN-EN 60076-6:2008 | IEC 60076-6:2007 | PN-EN IEC 60076-11:2019-01 | IEC 60076-11:2018 | ||
| 47 | Current transformers, Voltage transformers, Combined transformers | Short-circuit tests Range up to 100 kA rms / 250 kA peak Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 61869-1:2009 | IEC 61869-1:2007 | PN-EN 61869-2:2013-06 | IEC 61869-2:2012 | PN-EN 61869-3:2011 | IEC 61869-3:2011 | PN-EN 61869-4:2014-09 | IEC 61869-4:2013 | ||
| 48 | Current transformers, Voltage transformers, Combined transformers | Impulse voltage withstand test: lightning impulse up to Up = 1200 kV switching impulse up to Up = 900 kV power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 61869-1:2009 | IEC 61869-1:2007 | PN-EN 61869-2:2013-06 | IEC 61869-2:2012 | PN-EN 61869-3:2011 | IEC 61869-3:2011 | PN-EN 61869-4:2014-09 | IEC 61869-4:2013 | ||
| 49 | Current transformers, Voltage transformers, Combined transformers | Temperature rise tests Range up to 4 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 61869-1:2009 | IEC 61869-1:2007 | PN-EN 61869-2:2013-06 | IEC 61869-2:2012 | PN-EN 61869-3:2011 | IEC 61869-3:2011 | PN-EN 61869-4:2014-09 | IEC 61869-4:2013 | ||
| 50 | Current transformers, Voltage transformers, Combined transformers | Mechanical strength Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 61869-1:2009 | IEC 61869-1:2007 | PN-EN 61869-2:2013-06 | IEC 61869-2:2012 | PN-EN 61869-3:2011 | IEC 61869-3:2011 | PN-EN 61869-4:2014-09 | IEC 61869-4:2013 | ||
| 51 | Current transformers, Voltage transformers, Combined transformers | Internal arc fault Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 61869-1:2009 | IEC 61869-1:2007 | PN-EN 61869-2:2013-06 | IEC 61869-2:2012 | PN-EN 61869-3:2011 | IEC 61869-3:2011 | PN-EN 61869-4:2014-09 | IEC 61869-4:2013 | ||
| 52 | HV metal-enclosed busbars | Impulse voltage withstand test: lightning impulse up to Up = 1200 kV power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
ANSI/IEEE C 37.23:2015 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 53 | HV metal-enclosed busbars | Temperature rise tests Range up to 12 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
ANSI/IEEE C 37.23:2015 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 54 | HV metal-enclosed busbars | Main circuit resistance Range from 10-5 Ω Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
ANSI/IEEE C 37.23:2015 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 55 | HV metal-enclosed busbars | Short-circuit tests Range up to 120 kA rms / 300 kA peak Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
ANSI/IEEE C 37.23:2015 | PN-EN 62271-1:2018-02 | PN-EN 62271-1:2018-02/A1:2022-06 | IEC 62271-1:2017+AMD1:2021 | ||
| 56 | Portable equipment for earthing or earthing and short-circuiting | Short-circuit tests Range up to 120 kA rms / 300 kA peak Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 61230:2011 | ||
| 57 | Insulating sticks for voltages from 1 kV to 750 kV | Impulse voltage withstand test: power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60832-1:2010 | PN-EN 60832-2:2010 | ||
| 58 | Pliers and grippers for voltages above 1 kV | Impulse voltage withstand test: power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PB 102 issue No. 6 of 2011-11-02 | ||
| 59 | Insulation platforms | Impulse voltage withstand test: power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PB 103 issue No. 6 of 2011-11-02 | ||
| 60 | Voltage indicators | Impulse voltage withstand test: power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 61243-1:2022-01 | PN-EN 61243-2:2002 | PN-EN 61243-2:2002/A2:2003 | PN-EN 61243-3:2015-04 | PN-EN 61243-5:2004 | ||
| 61 | Phase comparators | Impulse voltage withstand test: power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 61481-1:2015-04 | PN-EN 61481-2:2015-04 | ||
| 62 | Insulating material sleeves for live work | Impulse voltage withstand test: power frequency 50 Hz up to Ud = 30 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60984:1998 | PN-EN 60984:1998/A1:2004 | ||
| 63 | Electro-insulating rubber mats | Impulse voltage withstand test: power frequency 50 Hz up to Ud = 30 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 61111:2009 | ||
| 64 | Electrical insulating gloves for live work | Impulse voltage withstand test: power frequency 50 Hz up to Ud = 30 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60903:2006 | ||
| 65 | Electrically insulating wellingtons and half-shoes | Impulse voltage withstand test: power frequency 50 Hz up to Ud = 30 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 50321-1:2018-05 | ||
| 66 | Alternating-current low-voltage circuit-breakers | Temperature rise tests Range up to 10 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60947-2 :2018-01 | PN-EN 60947-2 :2018-01/A1:2020-06 | PN-EN IEC 60947-1 :2021-07 | IEC 60947-1:2020 | ||
| 67 | Alternating-current low-voltage circuit-breakers | Impulse voltage withstand test: lightning impulse up to Up = 25 kV power frequency 50 Hz up to Ud = 5 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60947-2 :2018-01 | PN-EN 60947-2 :2018-01/A1:2020-06 | PN-EN IEC 60947-1 :2021-07 | IEC 60947-1:2020 | ||
| 68 | Alternating-current low-voltage circuit-breakers | Short-circuit tests Range up to 100 kA rms / 230 kA peak Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60947-2 :2018-01 | PN-EN 60947-2 :2018-01/A1:2020-06 | PN-EN IEC 60947-1 :2021-07 | IEC 60947-1:2020 | ||
| 69 | Contactors and motor-starters | Temperature rise tests Range up to 10 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 60947-1:2021-07 | IEC 60947-1:2020 | PN-EN IEC 60947-4-1:2019-05 | PN-EN IEC 60947-4-3:2014-09 | ||
| 70 | Contactors and motor-starters | Impulse voltage withstand test: lightning impulse up to Up = 25 kV power frequency 50 Hz up to Ud = 5 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 60947-1:2021-07 | IEC 60947-1:2020 | PN-EN IEC 60947-4-1:2019-05 | PN-EN IEC 60947-4-3:2014-09 | ||
| 71 | Contactors and motor-starters | Making and breaking capacity Range up to 63 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 60947-1:2021-07 | IEC 60947-1:2020 | PN-EN IEC 60947-4-1:2019-05 | PN-EN IEC 60947-4-3:2014-09 | ||
| 72 | Contactors and motor-starters | Short-circuit tests Range AC: up to 100 kA rms / 230 kA peak / AC: up to and including 100 kA rms / 230 kA peak Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 60947-1:2021-07 | IEC 60947-1:2020 | PN-EN IEC 60947-4-1:2019-05 | PN-EN IEC 60947-4-3:2014-09 | ||
| 73 | Contactors and motor-starters | Mechanical endurance Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 60947-1:2021-07 | IEC 60947-1:2020 | PN-EN IEC 60947-4-1:2019-05 | PN-EN IEC 60947-4-3:2014-09 | ||
| 74 | Low-voltage switches, disconnectors, switch-disconnectors and fuse-combination units, Low-voltage control circuit devices and switching elements - electromechanical control circuit devices, Low-voltage multiple function equipment - transfer switching equipment | Temperature rise tests Range up to 10 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 60947-3:2021-07 | IEC 60947-3:2020 | PN EN 60947-5-1:2018-02 | PN-EN 60947-6-1:2009 | PN-EN IEC 60947-6-1:2023-10 | PN-EN IEC 60947-1:2021-07 | IEC 60947-1:2020 | ||
| 75 | Low-voltage switches, disconnectors, switch-disconnectors and fuse-combination units, Low-voltage control circuit devices and switching elements - electromechanical control circuit devices, Low-voltage multiple function equipment - transfer switching equipment | Impulse voltage withstand test: lightning impulse up to Up = 25 kV power frequency 50 Hz up to Ud = 5 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 60947-3:2021-07 | IEC 60947-3:2020 | PN EN 60947-5-1:2018-02 | PN-EN 60947-6-1:2009 | PN-EN IEC 60947-6-1:2023-10 | PN-EN IEC 60947-1:2021-07 | IEC 60947-1:2020 | ||
| 76 | Low-voltage switches, disconnectors, switch-disconnectors and fuse-combination units, Low-voltage control circuit devices and switching elements - electromechanical control circuit devices, Low-voltage multiple function equipment - transfer switching equipment | Short-circuit tests Range up to 100 kA rms / 230 kA peak Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 60947-3:2021-07 | IEC 60947-3:2020 | PN EN 60947-5-1:2018-02 | PN-EN 60947-6-1:2009 | PN-EN IEC 60947-6-1:2023-10 | PN-EN IEC 60947-1:2021-07 | IEC 60947-1:2020 | ||
| 77 | Low-voltage switches, disconnectors, switch-disconnectors and fuse-combination units, Low-voltage control circuit devices and switching elements - electromechanical control circuit devices, Low-voltage multiple function equipment - transfer switching equipment | Mechanical endurance Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 60947-3:2021-07 | IEC 60947-3:2020 | PN EN 60947-5-1:2018-02 | PN-EN 60947-6-1:2009 | PN-EN IEC 60947-6-1:2023-10 | PN-EN IEC 60947-1:2021-07 | IEC 60947-1:2020 | ||
| 78 | Low-voltage switches, disconnectors, switch-disconnectors and fuse-combination units, Low-voltage control circuit devices and switching elements - electromechanical control circuit devices, Low-voltage multiple function equipment - transfer switching equipment | Switching durability Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 60947-3:2021-07 | IEC 60947-3:2020 | PN EN 60947-5-1:2018-02 | PN-EN 60947-6-1:2009 | PN-EN IEC 60947-6-1:2023-10 | PN-EN IEC 60947-1:2021-07 | IEC 60947-1:2020 | ||
| 79 | Terminal blocks for copper conductors | Mechanical strength Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60947-7-1:2012 | IEC 60947-7-1:2009 | PN-EN 60947-7-2:2012 | IEC 60947-7-2:2009 | PN-EN IEC 60947-1:2021-07 | IEC 60947-1:2020 | ||
| 80 | Terminal blocks for copper conductors | Impulse voltage withstand test: lightning impulse up to Up = 25 kV power frequency 50 Hz up to Ud = 5 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60947-7-1:2012 | IEC 60947-7-1:2009 | PN-EN 60947-7-2:2012 | IEC 60947-7-2:2009 | PN-EN IEC 60947-1:2021-07 | IEC 60947-1:2020 | ||
| 81 | Terminal blocks for copper conductors | Temperature rise tests Range up to 1 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60947-7-1:2012 | IEC 60947-7-1:2009 | PN-EN 60947-7-2:2012 | IEC 60947-7-2:2009 | PN-EN IEC 60947-1:2021-07 | IEC 60947-1:2020 | ||
| 82 | Low-voltage switchgear and control gear assemblies | Temperature rise tests Range up to 12 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 61439-1:2021-10 | IEC 61439-1:2020 | PN-EN IEC 61439-2:2021-10 | IEC 61439-2:2020 | PN-EN IEC 61439-3:2025-09 | IEC 61439-3:2024 | PN-EN 61439-4:2013-06 | IEC 61439-4:2012 | PN-EN IEC 61439-5:2024-04 | IEC 61439-5:2023 | PN-EN 61439-6:2013-03 | IEC 61439-6:2012 | PN-EN IEC 61439-7:2020-10 | PN-EN IEC 61439-7:2024-04 | PN-E-05163:2002 | IEC/TR 61641:2014 | PN-EN IEC 62208:2024-04 | IEC 62208:2023 | ||
| 83 | Low-voltage switchgear and control gear assemblies | Impulse voltage withstand test: lightning impulse up to Up = 25 kV power frequency 50 Hz up to Ud = 15 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 61439-1:2021-10 | IEC 61439-1:2020 | PN-EN IEC 61439-2:2021-10 | IEC 61439-2:2020 | PN-EN IEC 61439-3:2025-09 | IEC 61439-3:2024 | PN-EN 61439-4:2013-06 | IEC 61439-4:2012 | PN-EN IEC 61439-5:2024-04 | IEC 61439-5:2023 | PN-EN 61439-6:2013-03 | IEC 61439-6:2012 | PN-EN IEC 61439-7:2020-10 | PN-EN IEC 61439-7:2024-04 | PN-E-05163:2002 | IEC/TR 61641:2014 | PN-EN IEC 62208:2024-04 | IEC 62208:2023 | ||
| 84 | Low-voltage switchgear and control gear assemblies | Short-circuit tests Range up to 120 kA rms / 250 kA peak Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 61439-1:2021-10 | IEC 61439-1:2020 | PN-EN IEC 61439-2:2021-10 | IEC 61439-2:2020 | PN-EN IEC 61439-3:2025-09 | IEC 61439-3:2024 | PN-EN 61439-4:2013-06 | IEC 61439-4:2012 | PN-EN IEC 61439-5:2024-04 | IEC 61439-5:2023 | PN-EN 61439-6:2013-03 | IEC 61439-6:2012 | PN-EN IEC 61439-7:2020-10 | PN-EN IEC 61439-7:2024-04 | PN-E-05163:2002 | IEC/TR 61641:2014 | PN-EN IEC 62208:2024-04 | IEC 62208:2023 | ||
| 85 | Low-voltage switchgear and control gear assemblies | Internal arc fault tests Range up to 60 kA Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 61439-1:2021-10 | IEC 61439-1:2020 | PN-EN IEC 61439-2:2021-10 | IEC 61439-2:2020 | PN-EN IEC 61439-3:2025-09 | IEC 61439-3:2024 | PN-EN 61439-4:2013-06 | IEC 61439-4:2012 | PN-EN IEC 61439-5:2024-04 | IEC 61439-5:2023 | PN-EN 61439-6:2013-03 | IEC 61439-6:2012 | PN-EN IEC 61439-7:2020-10 | PN-EN IEC 61439-7:2024-04 | PN-E-05163:2002 | IEC/TR 61641:2014 | PN-EN IEC 62208:2024-04 | IEC 62208:2023 | ||
| 86 | Low-voltage switchgear and control gear assemblies | Clearances and creepage distances Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 61439-1:2021-10 | IEC 61439-1:2020 | PN-EN IEC 61439-2:2021-10 | IEC 61439-2:2020 | PN-EN IEC 61439-3:2025-09 | IEC 61439-3:2024 | PN-EN 61439-4:2013-06 | IEC 61439-4:2012 | PN-EN IEC 61439-5:2024-04 | IEC 61439-5:2023 | PN-EN 61439-6:2013-03 | IEC 61439-6:2012 | PN-EN IEC 61439-7:2020-10 | PN-EN IEC 61439-7:2024-04 | PN-E-05163:2002 | IEC/TR 61641:2014 | PN-EN IEC 62208:2024-04 | IEC 62208:2023 | ||
| 87 | Low-voltage switchgear and control gear assemblies | Protection against unintentional direct contact with hazardous live parts Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 61439-1:2021-10 | IEC 61439-1:2020 | PN-EN IEC 61439-2:2021-10 | IEC 61439-2:2020 | PN-EN IEC 61439-3:2025-09 | IEC 61439-3:2024 | PN-EN 61439-4:2013-06 | IEC 61439-4:2012 | PN-EN IEC 61439-5:2024-04 | IEC 61439-5:2023 | PN-EN 61439-6:2013-03 | IEC 61439-6:2012 | PN-EN IEC 61439-7:2020-10 | PN-EN IEC 61439-7:2024-04 | PN-E-05163:2002 | IEC/TR 61641:2014 | PN-EN IEC 62208:2024-04 | IEC 62208:2023 | ||
| 88 | Low-voltage switchgear and control gear assemblies | Lifting Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 61439-1:2021-10 | IEC 61439-1:2020 | PN-EN IEC 61439-2:2021-10 | IEC 61439-2:2020 | PN-EN IEC 61439-3:2025-09 | IEC 61439-3:2024 | PN-EN 61439-4:2013-06 | IEC 61439-4:2012 | PN-EN IEC 61439-5:2024-04 | IEC 61439-5:2023 | PN-EN 61439-6:2013-03 | IEC 61439-6:2012 | PN-EN IEC 61439-7:2020-10 | PN-EN IEC 61439-7:2024-04 | PN-E-05163:2002 | IEC/TR 61641:2014 | PN-EN IEC 62208:2024-04 | IEC 62208:2023 | ||
| 89 | Enclosures for electrical equipment, Electrical and electronic equipment | Degree of protection against external mechanical impacts IK up to IK10 / Environmental testing - Test Eh: Hammer tests Range up to IK10 Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 62262:2003 | PN-EN 60068-2-75:2015-01 | ||
| 90 | Enclosures for electrical equipment, Electrical and electronic equipment | Environmental testing - Test A: Cold Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60068-2-1:2009 | ||
| 91 | Enclosures for electrical equipment, Electrical and electronic equipment | Environmental testing - Test B: Dry heat Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60068-2-2:2009 | ||
| 92 | Enclosures for electrical equipment, Electrical and electronic equipment | Environmental testing - Test Cab: Damp heat, steady state Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60068-2-78:2013-11 | ||
| 93 | Enclosures for electrical equipment, Electrical and electronic equipment | Environmental testing - Test Db: Damp heat, cyclic Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60068-2-30:2008 | ||
| 94 | Enclosures for electrical equipment, Electrical and electronic equipment | Resistance to corrosion in a salt mist atmosphere Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN IEC 60068-2-11:2021-11 | PN-EN 60068-2-52:2018-05 | ||
| 95 | Enclosures for electrical equipment, Electrical and electronic equipment | Degree of protection up to IP 68 Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60529:2003 | PN-EN 60529:2003/A2:2014-07 excluding cl. 14 | IEC 60529:1989 | IEC 60529:1989/AMD 1:1989 | IEC 60529:1989/AMD 2:2013 excluding cl. 14 | ||
| 96 | Enclosures for electrical equipment, Electrical and electronic equipment | Impulse voltage withstand test: lightning impulse up to Up = 1200 kV switching impulse up to Up = 900 kV power frequency 50 Hz up to Ud = 300 kV Material / product tested (calculated), Type of activity / parameter / characteristic tested (calculated), Reference documents (calculated) |
PN-EN 60060-1:2011 | IEC 60060-1:2010 | PN-EN 60060-2:2011 | IEC 60060-2:2010 | ||
Reference standards (128)
ANSI/IEEE C 37.23:2015
IEC 60060-1:2010
IEC 60060-2:2010
IEC 60076-11:2018
IEC 60076-1:2011
IEC 60076-2:2011
IEC 60076-3:2013+AMD1:2018 CSV
IEC 60076-4:2002
IEC 60076-5:2006
IEC 60076-6:2007
IEC 60529:1989
IEC 60529:1989/AMD 1:1989
IEC 60529:1989/AMD 2:2013 excluding cl. 14
IEC 60947-1:2020
IEC 60947-3:2020
IEC 60947-7-1:2009
IEC 60947-7-2:2009
IEC 61439-1:2020
IEC 61439-2:2020
IEC 61439-3:2024
IEC 61439-4:2012
IEC 61439-5:2023
IEC 61439-6:2012
IEC 61869-1:2007
IEC 61869-2:2012
IEC 61869-3:2011
IEC 61869-4:2013
IEC 62208:2023
IEC 62271-100:2021
IEC 62271-101:2021
IEC 62271-102:2018+AMD1:2022
IEC 62271-103:2021
IEC 62271-105:2021
IEC 62271-106:2021
IEC 62271-111:2019
IEC 62271-1:2017+AMD1 :2021
IEC 62271-1:2017+AMD1:2021
IEC 62271-200:2021
IEC 62271-200:2021/AMD1:2024
IEC 62271-201:2014
IEC 62271-202:2022
IEC 62271-203:2022
IEC/TR 61641:2014
PB 102 issue No. 6 of 2011-11-02
PB 103 issue No. 6 of 2011-11-02
PN EN 60947-5-1:2018-02
PN-E-05163:2002
PN-E-91062-1:1998
PN-E-91062-2:1998
PN-EN 50321-1:2018-05
PN-EN 60060-1:2011
PN-EN 60060-2:2011
PN-EN 60068-2-1:2009
PN-EN 60068-2-2:2009
PN-EN 60068-2-30:2008
PN-EN 60068-2-52:2018-05
PN-EN 60068-2-75:2015-01
PN-EN 60068-2-78:2013-11
PN-EN 60076-1:2011
PN-EN 60076-2:2011
PN-EN 60076-3:2014-02
PN-EN 60076-3:2014-02/A1:2018-09
PN-EN 60076-4:2004
PN-EN 60076-5:2009
PN-EN 60076-6:2008
PN-EN 60137:2018-02
PN-EN 60383-1:2005
PN-EN 60383-1:2024-04
PN-EN 60529:2003
PN-EN 60529:2003/A2:2014-07 excluding cl. 14
PN-EN 60832-1:2010
PN-EN 60832-2:2010
PN-EN 60903:2006
PN-EN 60947-2 :2018-01
PN-EN 60947-2 :2018-01/A1:2020-06
PN-EN 60947-6-1:2009
PN-EN 60947-7-1:2012
PN-EN 60947-7-2:2012
PN-EN 60984:1998
PN-EN 60984:1998/A1:2004
PN-EN 61109:2010
PN-EN 61111:2009
PN-EN 61230:2011
PN-EN 61243-2:2002
PN-EN 61243-2:2002/A2:2003
PN-EN 61243-3:2015-04
PN-EN 61243-5:2004
PN-EN 61439-4:2013-06
PN-EN 61439-6:2013-03
PN-EN 61481-1:2015-04
PN-EN 61481-2:2015-04
PN-EN 61869-1:2009
PN-EN 61869-2:2013-06
PN-EN 61869-3:2011
PN-EN 61869-4:2014-09
PN-EN 62262:2003
PN-EN 62271-106:2021-09
PN-EN 62271-1:2018-02
PN-EN 62271-1:2018-02/A1 :2022-06
PN-EN 62271-1:2018-02/A1:2022-06
PN-EN 62271-200:2022-02
PN-EN 62271-200:2022-02/A1:2025-04
PN-EN 62271-201:2014-12
PN-EN IEC 60068-2-11:2021-11
PN-EN IEC 60076-11:2019-01
PN-EN IEC 60947-1 :2021-07
PN-EN IEC 60947-1:2021-07
PN-EN IEC 60947-3:2021-07
PN-EN IEC 60947-4-1:2019-05
PN-EN IEC 60947-4-3:2014-09
PN-EN IEC 60947-6-1:2023-10
PN-EN IEC 61243-1:2022-01
PN-EN IEC 61439-1:2021-10
PN-EN IEC 61439-2:2021-10
PN-EN IEC 61439-3:2025-09
PN-EN IEC 61439-5:2024-04
PN-EN IEC 61439-7:2020-10
PN-EN IEC 61439-7:2024-04
PN-EN IEC 62208:2024-04
PN-EN IEC 62271-100:2022-04
PN-EN IEC 62271-101:2022-04
PN-EN IEC 62271-102:2018-10
PN-EN IEC 62271-102:2018-10/A1:2023-01
PN-EN IEC 62271-103:2024-04
PN-EN IEC 62271-105:2024-04
PN-EN IEC 62271-202:2023-02
PN-EN IEC 62271-203:2023-02
PN-G-42021:1997